Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
139/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
Setp_Stage referred to the current setpoint (Wcurrent)
MaxTmeMod Cold start thermal shock protection, max. time per step (modu-
lating)
1..63 min Service 3 min x x
MaxTmeStage Cold start thermal shock protection, maximum time per step
(multistage)
1..63 min Service 3 min x x
ThresholdOff Cold start thermal shock protection deactivation level referred
to the current setpoint (Wcurrent)
0..100 % Wcurrent Service 80 % x x
AdditionalSens Selection for additional sensor (cold start thermal shock pro-
tection)
deactivated
Pt100
Pt1000
Ni1000
Service deactivated x x
Setp AddSensor Setpoint for additional sensor (cold start thermal shock protec-
tion)
0..450 °C Service 60 °C x x
Release Stages Cold start thermal shock protection load step stage mode (mul-
tistage operation)
no release
release
Service release x x
Configuration General configuration of the load controller User x x
LC_OptgMode Operating mode with load controller ExtLC X5-03
IntLC
IntLC Bus
IntLC X62
ExtLC X62
ExtLC Bus
User IntLC x x
Sensor Select Select actual value input
E1 → Pt100, TL act.
E4 → Pt1000, TL act.
E4 → Ni1000, TL act.
E2 → Temp, TL inact.
E2 → Pressure, TL inact.
E1 → Pt100 for controller + TL and E4 → Pt1000 for TL
E1 → Pt100 for controller + TL and E4 → Ni1000 for TL
No input
Pt100
Pt1000
Ni1000
TempSensor
PressSensor
Pt100Pt1000
Pt100Ni1000
NoSensor
Service Pt100 x x
Measur-
eRangePtNi
End of measurement range for sensor at input X60 150 °C / 302 °F
400 °C / 752 °F
Service 150 °C / 302
°F
x x
Ext Inp X61 U/I Configuration of external input X61 4..20 mA
2..10 V
0..10 V
Service 0..10 V x x