Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
140/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
MRange Temp-
Sens
End of temperature measuring range for input X61 0..2000 °C Service 90 °C x x
MRange Press-
Sens
End of pressure measuring range for input X61 0..99.9 bar Service 2 bar x x
Ext Inp X62 U/I Configuration of external input X62 4..20 mA
0 / 2..10 V
Service 4..20 mA x x
Ext MinSetpoint Accepted preselected minimum external setpoint for X62 / bus 0..100 % ScaleHIcurrent Service 0 % x x
Ext MaxSetpoint Accepted preselected maximum external setpoint for X62 / bus 0..100 % ScaleHIcurrent Service 60 % x x
Adaption Adapting the controlled system User x x
StartAdaption User x x
AdaptionLoad Adaption load 40..100 % User 100 % x x
SW Version SW version of internal load controller 0..65535 User --- x x
AZL Settings for the display and operating unit User x x
Times AZL5...-specific time settings User x x
PasswordTime Validity of password 10..480 min OEM 120 min x x
Sum/WinterTime Setting the summer-/wintertime Manual
Automatic
User Automatic x x
Time EU/US Setting the summer-/wintertime US / EU S / W time EU
S / W time US
User S / W time
EU
x x
Language Selection of language English
German
Language 3
Language 4
Language 5
Language 6
User German x x
DateFormat Selection of date format (Day.Month.Year or Month-Day-Year) DD.MM.YY
MM-DD-YY
User DD.MM.YY x x
PhysicalUnits User x x
UnitTemperature Selection of display format °C or F Display °C
Display °F
User Display °C x x
UnitPressure Selection of display format bar or psi Display bar
Display psi
User Display bar x x
eBUS User x x
Address E-bus address of LMV5... 1..8 User 1 x x
SendCycleBU Cycle time for sending the burner control's operating data to
BAS
10..60 s User 30 s x x