Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
141/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
Modbus User x x
Address Modbus address of LMV5... 1..247 User 1 x x
Baudrate Modbus rate of transmission 19200 bit/s
9600 bit/s
User 19200 bit/s x x
Parity Modbus parity for LMV5... no
even
odd
User no x x
Timeout Maximum time with no communication. When this period of
time has elapsed, "Remote" changes to "Local"
0..7200 s User 30 s x x
Lokal / Remote Change of operating mode local / remote local
remote
User --- x x
Remote Mode Operating mode: Remote "off" / remote "on" / W3 Automatic
Burner on
Burner off
User --- x x
W3 External setpoint W3, in °C
External setpoint W3, in bar
0..2000 °C
0..100 bar
User --- x x
Display Contrast User x x
ProductID Displaying the HW version of the AZL5... User x x
ASN Type reference 1..15 characters User "AZL52.00A
1WH"
x x
ProductionDate Production date 01.01.00..31.12.99
01-01-00..12-31-99
User --- x x
SerialNumber Serial number 0..65535 User --- x x
ParamSet Code Preselected parameter set: customer code 0..255 User 20 x x
ParamSet Vers Preselected parameter set: version 0..65535 User 430 x x
SW Version SW version of AZL5... 0..65535 User --- x x
Actuators Settings for the actuators User x x
Addressing Addressing unaddressed actuators Service x x
1 AirActuator Actuator to be addressed becomes the air actuator Service x x
2 GasActuat(Oil) Actuator to be addressed becomes the gas actuator, or the
fuel actuator for dual fuel burners with one fuel actuator
Service x x
3 OilActuator Actuator to be addressed becomes the oil actuator Service x x
4 AuxActuator Actuator to be addressed becomes the auxiliary actuator Service x x
5 AuxActuator2 Actuator to be addressed becomes the auxiliary actuator Service x
6 AuxActuator3 Actuator to be addressed becomes the auxiliary actuator Service x
DirectionRot Service x x