Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
144/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
Configuration Service x x
Speed Service x x
Num Puls per R Number of pulses per revolution 3..6 Service 3 x x
Standardization Standardization process for fan speed deactivated
activated
Service --- x x
StandardizedSp Standardized speed: Speed corresponding to 100 % 1..6300 Service 1 x x
Setpoint Output Configuration of analog interface 0..20 mA
4..20 mA
Service 4..20 mA x x
Setteling Time Time between speed readjustment and speed acquisition for
long run commands
200...5000 ms OEM 16 x x
Fuel Meter Fuel counter controller Service x x
PulseValueGas Number of pulses per volume unit gas 0.0000..9999.9999 Imp/m³
0.00000..999.99999
Imp/ft³
Service 1 x x
PulseValueOil Number of pulses per volume unit oil 0.0000..9999.9999 Imp/l
0.0000..9999.9999
Imp/gal
Service 1 x x
Process Data User x x
Max Stat Dev Maximum speed deviation at the end of a run command 0..100 % User --- x x
Max Dyn Dev Maximum speed deviation when accelerating 0..100 % User --- x x
Num Dev >0.3% Number of speed deviations >0.3 % at the end of a run com-
mand
0..255 User --- x x
Num Dev >0.5% Number of speed deviations >0.5 % at the end of a run com-
mand
0..255 User --- x x
Absolute Speed Absolute speed 0..6553.5 User --- x x
ProductID User x x
ASN Type reference 1..15 characters User --- x x
ProductionDate Date of production 01.01.00..31.12.99
01-01-00..12-31-99
User --- x x
SerialNumber Serial number 0..65535 User --- x x
ParamSet Code Preselected parameter set: customer code 0..255 User 20 x x
ParamSet Vers Preselected parameter set: version 0..65535 User 430 x x
SW Version SW version of VSD 0..65535 User --- x x
O2 Module Settings for the O2 module User x
Configuration Service x
O2 Sensor Configuration of oxygen sensor no sensor Service no sensor x