Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
145/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
QGO20
SupAirTemp-
Sens
Configuration of supply air temperature input no sensor
Pt1000
Ni1000
Service no sensor x
FlueGasTemp-
Sens
Configuration of flue gas temperature input no sensor
Pt1000
Ni1000
Service no sensor x
Max-
TempFlGasGas
Switch-off limit of flue gas temperature 0..400 °C Service 400 °C x
Max-
TempFlGasOil
Switch-off limit of flue gas temperature 0..400 °C Service 400 °C x
Displayed
Values
User x
Actual O2 Value Actual O2 value 0..100 % User --- x
O2 Setpoint O2 setpoint 0...25 % User --- x
SupplyAirTemp Supply air temperature in °C -100..923 °C User --- x
FlueGasTemp Flue gas temperature in °C -100..923 °C User --- x
CombEfficiency Combustion efficiency 0...200 % User --- x
QGO Sensor-
Temp
Sensor temperature of QGO... in °C -100..923 °C User --- x
QGO Heatin-
gLoad
Control value of QGO... heating in 0.1 % 0..100 % User --- x
QGO Resistance Internal resistance of QGO's Nernst cell 0..1000 Ohm User --- x
ProductID User x
ASN Type reference 1..15 characters User "PLL52.110
A100"
x
ProductionDate Date of production 01.01.00..31.12.99
01-01-00..12-31-99
User --- x
SerialNumber Serial number 0..65535 User --- x
ParamSet Code Preselected parameter set: customer code 0..255 User 20 x
ParamSet Vers Preselected parameter set: version 0..65535 User 430 x
SW Version SW version of O2M 0..65535 User --- x
SystemConfig Settings for LMV5... system configuration User x x
LC_OptgMode Operating mode with load controller ExtLC X5-03
IntLC
IntLC Bus
User IntLC x x