EasyManua.ls Logo

Siemens LMV52.200B1 - Page 182

Siemens LMV52.200B1
327 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
182/327
Building Technologies Basic Documentation LMV5... CC1P7550en
9 Commissioning instructions for the LMV5 22.05.2018
P
G
= 30 mbar
P
W
= 15 mbar
P
atm
= 1013 mbar
V = 3 l
Q
Leck
= 50 l/h
(30 - 15) mbar 3 l 3600 s / h
t
Test
=
= 3,2 s
1013 mbar 50 l/h
Result: The test time to be set is 4 seconds
P
G
= 30 mbar
P
W
= 15 mbar
P
atm
= 1013 mbar
V = 3 l
t
Test
= 4 s
(30 - 15) mbar 3 l 3600 s/h
Q
Leck
=
= 40,0 l/h
1013 mbar 4 s
Result: The detected leakage rate is 40 l/h
Example 1 (calculation
of test time)
Example 2 (determination
of detectable leakage
rate)

Table of Contents

Related product manuals