DF8046
DF8046 is a module providing 4 supervised inputs (normally-open balanced inputs)
designed for migration of CS100/DMS7000 Multiplexer systems with B1G030 line
supervision boards.
See NK823x hardware installation [➙ 42] for more information on the connection of
I/O modules to the NK823x.
DF8090 Power Supply Supervision
DF8090 is a module designed for monitoring a 12V DC power supply. It can detect
the conditions listed below, shown on the DF8090 local panel and report them to
NK823x, and in turn to management station (see the following):
⚫ Mains failure (no 220VAC)
⚫ Battery low
⚫ Power supply failure (trouble with AC/DC converter)
⚫ Battery protection fuse blown (internal micro-fuse type MSF 3.15A/250V)
See figure
NK823x power connections
(see NK823x hardware installation [➙ 42])
for the NK823x power connections using the power supervision module.
Note: Locally connected DF8000 I/O modules are only supported with NK823x
with build state 10 or higher (NKM8001-A2 mainboard).
For more information about the DF8000 Input/Output modules, including
installation details, see documents
DF8000 Datasheet (document
no.A6V10081184)