Maintenance and diagnostics
9
The NW8204 diagnostic tool
69
Building Technologies
A6V10062437_a_en
CPS Fire Safety
30.01.2019
The information in this file is not meant to be used by field engineers on site. In
case of technical problems, the DIAGNO.LOG file can be sent to technical support
for further analysis.
EEProm.LOG
You create this file by clicking the Save EEProm on File button. This file contains
information about the NK8000 hardware status stored on the EEPROM. For
example, if it was not possible to use the serial interface on COM3 because the
serial add-on board is broken, that message is saved into the EEPROM.
Note: Every time you click the Save EEProm on File button, the existing
EEProm.LOG file is overwritten.
A detailed description of the EEPROM log entries is provided in the table below.
ID
Message text
Meaning
0
EV_EEPROM_NULL
1
EV_EEPROM_INIT
EEPROM initialization
2
EV_EEPROM_START
NK8000 unit restart
3
EV_EEPROM_NOT_ALIGNED
EEPROM not aligned
4
EV_EEPROM_NO_ETH_INIT
Ethernet initialization failed
5
EV_EEPROM_TAMPER_OPEN
NK8000 unit box opened
6
EV_EEPROM_TAMPER_CLOSE
NK8000 unit box closed
8
EV_EEPROM_NO_SER0_INIT
COM1 initialization failed
9
EV_EEPROM_NO_SER1_INIT
COM2 initialization failed
10
EV_EEPROM_NO_SER2_INIT
COM3 initialization failed
11
EV_EEPROM_NO_SER3_INIT
COM4 initialization failed
12
EV_EEPROM_SER0_ERROR
COM1 error
13
EV_EEPROM_SER1_ERROR
COM2 error
14
EV_EEPROM_SER2_ERROR
COM3 error
15
EV_EEPROM_SER3_ERROR
COM4 error
16
EV_EEPROM_DATE_TIME
Date and time changed within delta threshold
17
EV_EEPROM_NEW_DATE_TIME
Date and time changed over delta threshold
18
EV_EEPROM_RESET
Reset command
19
EV_EEPROM_EMERGENCY
Restart in emergency mode
20
EV_EEPROM_FTP_SESSION
FTP session opened
21
EV_EEPROM_CONFIG_CHANGE
Configuration file changed
22
EV_EEPROM_SW_CHANGE
Software version changed
23
EV_EEPROM_CPU_CHANGE
CPU changed
24
EV_EEPROM_ETH_PNP_UPDATE
Ethernet EEPROM update
25
EV_EEPROM_ETH_PNP_ERROR
Ethernet EEPROM update failed
34
EV_EEPROM_DLL_LOAD_FAILED
DLL load failure
35
EV_EEPROM_DLL_EXCLUDED
DLL excluded from round-robin schedule
36
EV_EEPROM_DLL_OVERRUN
DLL response time over threshold 1
37
EV_EEPROM_DLL_VER_ERR
DLL version error
38
EV_EEPROM_DLL_INIT_ERR
DLL initialization error
39
EV_EEPROM_DLL_OVERTIME
DLL response time over threshold 2
40
EV_EEPROM_DLL_TIMEOUT
DLL response time over threshold 3
41
EV_EEPROM_DLL_EVENT
DLL diagnostic event
42
EV_EEPROM_HW_MISMATCH
PIC24 microcontroller init detected a hardware
version different from version in EEPROM