Hardware installation
5
NK823x hardware installation
46
Building Technologies A6V10062437_a_en
Fire Safety & Security Products 30.06.2013
5.3 NK823x hardware installation
Installation
1. Install the NK82xx unit on the DIN rail.
2. Connect subsystems:
Subsystem lines using the standard RS232 interfaces on COM1 - COM4.
Note: Only COM1 and COM2 are available on NK8231 and NK8232.
If used in place of COM1, the RS485 interface is on X104.
If used in place of COM2, the RS485 interface is on X105.
3. If used, connect the power supply supervision module DF8090.
4. If used, connect the onboard I/O signals.
5. Connect power supply.
See Figure
Power connections
if using a DF8090 power supply supervision
module.
WARNING
Do not connect or disconnect any device when the device is powered on!
Top view
Back
6 7 851
2
3
4
NK823x electrical interfaces (top view)
Item Name Description
1 X1 USB
2 X2 Ethernet 2
3 X3 Ethernet 1
4 X101 1 output
5 X102 3 inputs

Table of Contents