1.1 Interactions
The unit can be programmed to support interactions between the connected
subsystems: when a specified message is received from a source subsystem, one
or more commands are generated for a destination subsystem according to the
programmed interaction logic.
Interactions can be
local
or
network-wide
:
⚫ Local interactions only involve the subsystems connected to a single unit.
⚫ Network-wide interactions involve subsystems connected on different units,
which coordinate the interaction task over the network. Network-wide
interactions require units supporting the BACnet protocol.
Note: NK8000 units are not certified as part of an EN54-2 fire detection system.
Therefore, the interactions should only be used in applications where they are not
in conflict with EN54 standards or national guidelines or regulations (e.g., not for
common control of remote transmission devices).
Both local and network-wide interactions are supported for a restricted list of
subsystems:
⚫ FS20 Sinteso Fire control units (this subsystem is not supported by NK822x)
⚫ FS720 Cerberus PRO Fire control units (this subsystem is not supported by
NK822x), excluding FC721, which does not support BACnet connections to
management stations
⚫ STT20 Fire control unit (this subsystem is not supported by NK822x)
⚫ CS11 AlgoRex
®
Fire control unit
⚫ CS1115 Fire control unit
⚫ FC330A Fire control unit
⚫ FC700A Fire control unit
⚫ SIGMASYS/D100 Fire control unit
⚫ XLS FireFinder control unit
⚫ CS6 Guarto Intrusion control unit
⚫ Sintony SI410 Intrusion control unit
⚫ DF8000/CF9000 I/O modules
⚫ MK7022 Cerloop Interface
⚫ Philips Burle CCTV switcher
For details on interactions, see the
Network Connectivity Guide
(document
no.A6V10359485).