2
System limits
NS8210 driver system limits
14
Building Technologies
A6V10062437_a_en
CPS Fire Safety
30.01.2019
2 System limits
The following describes the system limits for the NK82xx units and the
corresponding NS82xx drivers for DMS8000 (MM8000 and MK8000) systems. For
detailed information about supported subsystem software versions see the
NK8000
Release Notes
(document n.A6V10062453.)
2.1 NS8210 driver system limits
NS8210 Ethernet Port connections (CMSDL/IP and CEI 79-5)
Currently, there is a limit of 500 NK82xx units per NS8210.
Note: Please contact customer support for configurations above 100 NK82xx.
NS8210 Transport protocols
NS8210 supports the transport protocols CMSDL/IP or CEI 79-5 for communication
with the Ethernet Ports.
Note: The cryptography option is only supported with the CEI 79-5 protocol.
Multiple host configurations are only supported with the CMSDL/IP protocol.
2.2 NS8011 driver system limits
NS8011 Ethernet Port connections (BACnet/IP)
Currently, there is a limit of 64 BACnet/IP connections per Server/FEP Station.
NS8011 Transport protocols
NS8011 supports the BACnet/IP protocol for communication with the NK8225,
NK8232, and NK8235.
Note: Encryption is not supported.
Subsystems supported
Same as interactions, refer to the list [➙ 12].