On
: critical/hardware fault.
Diagnostics (yellow LED)
Internal interface diagnostics:
⚫
Off
: status OK.
⚫
Blinking (fast)
: booting operating system after restart.
⚫
Blinking (1 flash)
: missing or insufficient license.
⚫
Blinking (2 flashes)
: trouble with the I
2
C bus to I/O modules.
⚫
Blinking (3 flashes)
: not used
⚫
Blinking (4 flashes)
: trouble with the serial/network interface.
⚫
Blinking (5 flashes)
: trouble with DLL or RCLOCK file(s).
⚫
Blinking (6 flashes)
: Modbus GW trouble.
– SW trouble.
– No communication to FS20/FS720 or to the Modbus Master/Client.
– No NK8237 or FS20/FS720 registers reading (Modbus Master watchdog
expired).
⚫
On
: critical/hardware fault.
Right Side LEDs
The four LEDs on the right side are from top to bottom:
3.2.2 Internal DIP switches
The internal DIP switches (S101) enable a download session via FTP using a
default IP.
Default mode/network access: If DIP switch 1 is ON, an FTP connection
occurs by default on the Ethernet 1 at the default IP address 192.168.9.41.
Default mode/network access: If DIP switch 2 is ON, an FTP connection
occurs by default on the Ethernet 2 at the default IP address 192.168.10.41.