Configuration
7
Configuring IP settings via NW8202
55
Building Technologies
A6V10062437_a_en
CPS Fire Safety
30.01.2019
7.2 Configuring IP settings via NW8202
This configuration must be performed before the NK8000 can be configured at the
client’s site. This procedure details how to send the IP configuration information;
that is, the IP address, Subnet mask, and Default address to the NK8000 via the
NW8202 Tool.
Note: This configuration procedure can be performed prior to shipping the
NK8000 to the client, or at a later time at the client’s site.
1. Set the Service PC IP address to 192.168.9.x (for example 192.168.9.254) and
the subnet mask to 255.255.255.0.
Note: Make note of the current IP address before replacing it with the new one.
2. Remove the cover of the NK82xx to be configured (NK822x: press the 4 white
tabs to the rear of the left and right sides of the unit and lift gently).
3. Open the NW8202 application by selecting NW8202.exe located in
<InstallationDir>\Utilities\NW8202 folder.
Note: On Windows 7/8 it might be needed to launch NW8202 with "Run as
administrator" (depending on your system security settings).
4. Select the Firmware Version NK823x.
Note: If NK823x is not indicated with a specific option, use latest NK822x.
5. Select the Download Mode: FTP (default) or Secure Download (encrypted data
transmission that makes use of TCP port 20500).
If FTP is selected, select the FTP Mode: Active (default) or Passive
(needed if a firewall is active in the PC).
6. Enter IP address, Subnet mask, and Default gateway in the corresponding
fields.
NW8202 IP configuration download tool