System limits
2
NK823x system limits
17
Building Technologies
A6V10062437_a_en
CPS Fire Safety
30.01.2019
control actions). Interactions are only possible between locally connected
subsystems.
For supported subsystems see Interactions [➙ 12]
Logical combinations: AND, OR, XOR, NOT
Delay of effects (wait): configurable 0…6500 sec
Max # of typical interactions (1-6 triggers, 1-4 effects): 500
Total # of field points used in triggers/effects: 5000
Max # of field points/interactions that can be combined in a trigger expression:
255
Modules locally connected via I
2
C
Up to 4 DF80xx modules in total
1 DF8090 Power supply supervision module
Up to 4 DF8020 relay output modules
Up to 4 DF8040 non supervised inputs modules
Up to 4 DF8045 supervised NC input modules
Up to 4 DF8046 supervised NO input modules
Note: Locally connected DF8000 I/O modules are only supported with NK823x
with build state 10 or higher (NKM8001-A2 mainboard; check the last two digits
after the part no. on the NK823x type label).