NK822x hardware installation
See LON interface [➙ 21] for additional information.
LON TP/FT-10 network segment characteristics.
Max. cable length (UTP Cat.4) [m]
2 x 100Ω, 1/8W
at each end of
segment
1 x 50Ω, 1/8W
at centre of segment
Max. number of nodes per segment
NK822x has a built-in termination resistor (100Ω) for a doubly terminated bus
topology that can be enabled by closing the internal jumper JP6.
See Internal jumpers [➙ 19] and LON interface [➙ 21].
Note: Please refer to the Echelon Manual for detailed specification on how to set
up a LON network: http://www.echelon.com/Support/documentation/, section:
Engineering Bulletins > Media & Wiring.
DIN Rail Installation
The modules are supplied in a plastic box that can be easily attached to the DIN
rail by hooking it on the top of the rail and pressing it in on the opposite side. To
detach the box, pull downward on the tab located at the rear of the module. The I/O
modules are mounted the same way.
Note: Before removing the box, carefully disconnect the flat cable (bus) of the I
2
C
module, as well as the power supply cables.