B-3
Manual OP5, OP15
( ) J31069-D0840-U001-A2-7618
Message Cause Action
$ 005 Internal error
$ 006 Error during data transfer in Down-
load mode
(message with two variables)
Var. 1 Status display
Var. 2
1 Internal error
3 Timeout error
5 Parity error
6 Framing error
7 Overrun error
8 Line interruption
9 Receive buffer overflow
10 Wrong control character
11 Internal error
Check connection, repeat download
$ 040 No response from PLC
– Cable defective or not
plugged in
– Character delay time too
short (FAP only)
– Check physical connection
– Modify and repeat download configu-
ration or PLC program
$ 041 Temporary driver error – Restart PC
– Download configuration
$ 100 Invalid RAM contents
$ 104 Download mode canceled by pres-
ing a key
$ 106 Serious error eliminated and key
pressed
$ 108 Mode change
$ 110 Mode change
$ 114 PLC cold restart
$ 115 Establishment of logical link
$ 117 Connection to PLC OK again fol-
lowing a fault
$ 119 Automatic start of OP (password
list is not compulsorily deleted)
$ 125 Language changed by standard
screen or PLC job
$ 131 Mode change
$ 133 Mode change
System Messages