Parameters required to realize the full function:
Building Automation Device
PL-Link Data Acquisition
Fan Speed Setpoint Manager FSSM
FSSM Configuration Data
Geographical Zone 24.6.1
PrioThreshFanSpeedUserLocked 7
Room Group 24.6.1
LTE IR (Auto)
LTE IR (33.3%)
LTE IR (Auto)
LTE W (false)
LTE IR (8)
LTE W (0%)
BA-Model
Room Control Room 1
Analog-Proc-Value FanSpeedEff
represent
FanSpeedEff
FanSpeedUserEff
FanSpeedUserLocked
FanSpeedEffWhy
FanSpeedUserMinIN
FanSpeedUser
PrioDirectControl 8
LTE W (100%)
FanSpeedUserMaxIN
PL-Link RU-B Room Unit
User FanSpeed Settings UFS
RoomGroup 24.6.1
FanSpeedUserMinIN
FanSpeedUser
FanSpeedUserEff
UFS Configuration Data
UFS Discovery & Diagnostic Data
FanSpeedUserLocked
User HVAC Display UHD
RoomGroup 24.6.1
FanSpeedEff
Management Data
UHD Discovery & Diagnostic Data
FanSpeedEffWhy
LTE IR (...)
FanSpeedUserMaxIN
represent
Config-Property-Client
Property_W (3)
TmpFanModeRemainTime
Management Data
FanBoostReq
KitchenHoodReq
FirePlaceReq
LTE IR (Trigger)
LTE IR (Trigger)
LTE IR (Trigger)
TmpFanModeRemainTime
LTE IR (15min)
TmpFanMode
LTE IR (FirePlace)
UFS Configuration Data
[cASA-4.2-100-N]
new optional UFS
output process signals
for temporary HRV fan
operation
}
{
FanBoostReq
ResetTmpFanReq
LTE IR (Trigger)
LTE IR (Trigger)
FirePlaceReq
LTE IR (Trigger)
KitchenHoodReq
LTE IR (Trigger)
ResetTmpFanReq
LTE IR (Trigger)
LTE IR (Auto)
LTE IR (33.3%)
[cASA-4.2-100-N]
new optional UHD
input process signals
for temporary HRV fan
operation
NumberOfSteps
LTE IR (15min)
LTE IR (Auto)
LTE W (false)
TmpFanMode
LTE IR (FirePlace)
[cASA-4.2-100-N]
new optional FSSM
input process signals
for temporary HRV fan
operation
{
}
[cASA-4.2-100-N]
new optional FSSM
output process signals
for temporary HRV fan
operation
represent
Analog-Calc-Value ManualFanSpeed
Binary-Calc-Value ResetTmpFanRequest
Binary-Calc-Value KitchenHoodRequest
Binary-Calc-Value FirePlaceRequest
Binary-Calc-Value FanBoostRequest
PL-1:PR=FSSM.
FanBoostReq;
GEO=24.6.1;
I/O-Address
Present-Value Active
Update-Count n
Binary-Calc-Value ManualFanMode
Multistate-Proc-Value TemporaryFanMode
PL-1:PR=FSSM.
TmpFanMode;
GEO=24.6.1;
I/O-Address
Present-Value
FirePlaceMode
None
FanBoostMode
FirePlaceMode
KitchenHoodMode
State-Text
Analog-Proc-Value TemporaryFanRemainTime
PL-1:PR=FSSM.
TmpFanMode
RemainTime;
GEO=24.6.1;
I/O-Address
Present-Value 15 min
represent
represent
RU Device Object
Configuration Data
EnableFanBoostOp true
EnableFirePlaceOp
true
EnableKitchenHoodOp
true
[cASA-4.2-100-N]
parameters to enable/
disable operation of
temporary fan modes
at runtime
Temporary mode