Appendix
Parameters
10
A6V11471220_en--_e
10 Appendix
10.1 Parameters
Parameters
Description
Default
P01
Backlighting level: 1, 2, …, 10
5
P02
Standby page types: 1, 2, …, 5
1: room temperature
2: room temperature and time
3: room temperature, time and outside air
temperature
4: room temperature, time, outside air
temperature and customer logo
5: room temperature, time, outside air
temperature and relative humidity
1
P03
Room operator unit temperature
correction: -3.0…3.0 K
0.0 K
P04
Temperature unit: °C and °F
°C
P05
Date format:
DD-MM-YYYY;
MM-DD-YYYY;
YYYY-MM-DD
DD-MM-YYYY
Parameters
Description
Default
P01…P05
As above
As above
P51
Restart the room operator unit by pressing
button 6
N/A
10.2 Object list
ObjTy
pe
ObjIns
tance
ObjI
dx
Function
Block
Property
PI
D
Arra
ySiz
e
PDT/DPT
R/
W
LTE-
Servi
ce
Description
Comments
0
1
0
DeviceO
bject
PID_OBJEC
T_TYPE
1
1
U16 /
PDT_UNSIGNE
D_INT
R
----
Device object: SD-
T060.0601_EN_SARB
_Data_Acquisition
7.1.2.9.1
PID_SERIAL
_NUMBER
11
1
N16U32 /
PDT_GENERIC
_06,
[DPT_SerNum
(DPT_ID =
221.001)]
R
----
KNX Serial Number of
the device in which it
is contained
PID_MANUF
ACTURER_I
D
12
1
U16 /
PDT_UNSIGNE
D_INT
R
----
Code assigned by the
KNX Association to
identify the
manufacturer of the
device.
253 / 0x00FD =
Siemens Schweiz AG
PID_DEVICE
_CONTROL
14
1
B8 /
PDT_BITSET8
[DPT_Device_
Control
RW
----
VerifyMode Contol for
UserMemery_Write
Service is done via
this property. Bit2 is
KNX Standard:
chapter 3-5-1, clause
4.2.14
PID_DEVICE_CONTR
Parameters for standard
settings
Parameters for expert
settings