Appendix
Object list
10
53 | 70
(DPT_ID =
21.002)]
the Verify-Mode Flag.
When using
connectionless
UserMemWrite, then
verifyMode shall be
active
OL
chapter 3-5-2, clause
3.19
DM_UserMem_Write
PID_ORDER
_INFO
15
1
PDT_GENERIC
_10
DPT_OrderInfo
(DPT-ID =
60110.60002)
R
----
manufacturer specific
Order Information
DPT-ID out of
proprietary range, as
Specified in Synco
PID_ROUTIN
G_COUNT
51
1
U8 /
PDT_UNSIGNE
D_CHAR
RW
----
This Property shall
include the default
value for the hop
count. (This is a
parameter for the
Network Layer of the
device.). It shall be
used to adjust the
default value of the
hop count parameter
of the Network Layer
KNX Standard,
chapter 3-5-1, clause
4.3.2
PID_ROUTING_COU
NT
PID_PROG_
MODE
54
1
B8 /
PDT_BITSET8
RW
----
Bit 0 = Programming
Mode
all other bits reserved
for future use
PID_PRODU
CT_ID
55
1
PDT_GENERIC
_10
DPT_Product_I
dentification
(DPT-ID =
60110.60002)
R
----
manufacturer specific
device type
For this property,
Synco rules apply:
Serial Number, Device
Family, Device Variant
(concatenated)
DPT-ID out of
proprietary range, as
Specified in Synco
PID_MAX_A
PDU_LENGT
H
56
1
U16 /
PDT_UNSIGNE
D_INT
R
----
maximal supported
APDU-length for
management of the
device
Default = 60 bytes
PID_SUBNE
T_ADDR
57
1
U8 /
PDT_UNSIGNE
D_CHAR
R
----
Subnetwork Address
part (high octet) of the
Individual Address
PID_DEVICE
_ADDR
58
1
U8 /
PDT_UNSIGNE
D_CHAR
R
----
Device Address part
(low octet) of the
Individual Address
PID_IO_LIST
71
25
U16 /
PDT_UNSIGNE
D_INT[ ]
R
----
Array which lists for
each object index the
Object Type
acc. KNX Standard,
chapter 3/5/1
Resources,
PID_IOLIST
DevIdent
24
1
1
U16U32U8N8 /
PDT_GENERIC
_08
R
IR.re
q
Used for SARB
localization,
communication test.
Sent with an LTE-
InfoReport after power
up and periodically if
DevIdentAutoSend is
enabled
DevIdentAut
oSend
24
2
1
B1 /
PDT_BINARY_I
NFORMATION
B1 /
DPT_Enable
RW
----
Enables
PID_DEVICE_IDENT
to be sent
spontaneously at
power up and in
regular intervals
DPT definition: SD-
T060.0601_EN_SARB
_Data_Aquisition
7.1.2.9.3
DevIdentHop
CountType
24
3
1
N8 /
PDT_ENUM8
DPT_HopCount
RW
----
Defines the used hop
count for DevIdent:
0: PSD defined
1: 0
DPT definition: SD-
T060.0601_EN_SARB
_Data_Aquisition