Building Automation Device
PL-Link Data Acquisition
PL-Link Room Unit
System Clock SCLO (Master)
SCLO Configuration Data
Peripheral Zone 0
SCLOMode Master
LTE Broadcast
SystemClock SCLO (Slave)
LTE Broadcast
SystemClock
Management Data
SCLO Configuration Data
SCLO Discovery & Diagnostic Data
Peripheral Zone
0
RelToGMT
LTE IR (2010-05-1;Mon;10:36:28;SuTi)
LTE IR (120min)
LTE IR (2010-05-31;Mon;10:36:28;SuTi)
LTE IR (120min)
BA-Model
Control Program
SystemClock
RelToGMT
SCLOMode Slave
EnableSystemClockSetting false
SystemClockHeartbeat 10min
SystemClockTimeout 21min
LocalClock
2010-05-31
Mon;10:36:28
EnableSystemClockSetting false
Firmware
(OS)
Fixed configuration
Optional feature; no real use
case on PL-Link so far
=> not implemented in a 1st step
Fixed configuration
Optional feature; no real use
case on PL-Link so far
=> not implemented in a 1st step
Device-Object
Local-Time 10:36:28
Local-Date
31-05-2010; Monday
UTC-Offset
120
Daylight-Savings-Status
true