Building Automation Device
PL-Link Data Acquisition
PL-Link OEM specific HVAC Room Unit
RoomSetpoint Manager RSMHD
RSMHD Configuration Data
Geographical Zone 24.6.1
PrioThreshHVACModeUserLocked 8
Room Group 24.6.1
User HVAC Display UHD
RoomGroup 24.6.1
HVACModeEff
Management Data
UHD Configuration Data
UHD Discovery & Diagnostic Data
Geographical Zone 24.6.1
LTE IR(Economy)
LTE IR (Economy)
LTE IR (Manual, Economy)
LTE W (true)
LTE IR (...)
BA-Model
Control Program
Multistate-Process-Value
PL-1:PR=RSMHD.
HVACModeEff;
GEO=24.6.1;
I/O-Address
Present-Value
Economy
Present-Priority
7
Priority-Array
….
represent
HVACModeEff
HVACModeUserEff
HVACModeUserLocked
HVACModeEffWhy
PrioDirectControl 8
Why-Indication[16]
x
Update-Count n
Protection
Economy
Precomfort
Comfort
State-Text
Number-of-States
4
Multistate-Process-Value
PL-1:PR=RSMHD.
HVACModeDeterm;
GEO=24.6.1;
I/O-Address
Present-Value
HardwareContact
represent
Update-Count n
Auto
RUManualPermanent
RUManualTemporary
HardwareContact
State-Text
Number-of-States
4
HVACModeDeterm
LTE IR (HardwareContact)
HVACModeDeterm
LTE IR (HardwareContact)
I/O Data Acquisition
IO-Function
Switch
1..3
Multistate-Input-Object
Present-Value
EconomySwitch
[cASA-4.2-170-N]
new process signal to indicate
manual override of HVAC Mode via
a hardware contact
Manual override of HVACMode via
a hardware contact will normally
result in Present-Priority=7
In case of manual override of HVACMode via a hardware
contact it is recommended to lock HVAC Mode operation
on the Room Unit.
With Present-Priority < PrioThreshHVACModeUserLocked
the output HVACMOdeUserLocked will be true