Appendix
Object list
10
A6V11471220_en--_e
PDT_UNSIGNE
D_CHAR
U8 /
DPT_Value_1_
Ucount
d.ind
Index Discovery via
LTE-Read onto this
Property
T060.0601_EN_SARB
_Data_Aquisition:
7.1.2.10.1
KNX Standard,
chapter 3-5-1,
PID_OBJECT_INDEX
TempOutside
Eff
15
5
1
V16Z8 /
DPT_TempHV
ACAbs_Z
R
IR.in
d
Outside temperature
value provided by the
Automation Device (°
C) *)
Field Description Sup.
Unit Default
Temperature Outside
temperature value
M °C. cs
STATUS Bitset M
Bit 0 - OutOfService
Sensor out of service
M t/f false
Bit 1 - Fault Sensor
value is corrupted M t/f
false
Bit 2 - Overridden
Sensor is temporarily
overridden O t/f false
Bit 3 - InAlarm Sensor
is in alarm O t/f false
Bit 4 - AlarmUnAck
Acknowledgement of
alarm O t/f false
all other bits are
reserved
TempRoomE
ff
15
7
1
V16Z8/PDT_G
ENERIC_03/DP
T_TempHVAC
Abs_Z
R
IR.in
d
Resulting (may be
averaged) room
temperature value
provided by the
Automation Device (°
C) *)
TempRoomS
etpAbsEff
16
1
1
V16Z8 /
DPT_TempHV
ACAbs_Z
R
IR.in
d
Absolute Room
Temperature Setp
requested by the
user,calculated from
the HVACMode and
TempRoomSetpUserO
ffset
=> cASA-[T022.S031-
2]-SARB-Data-
Mapping-HVAC
HVACModeE
ff
16
3
1
N8Z8 /
DPT_HVACMo
de_Z
R
IR.in
d
Effective HVACMode
calculated by the
Automation Device
based on
HVACModeUser
request, Scheduler
etc.
ComfortProlo
ngEff
16
8
1
DPT_State
R
IR.in
d
information if comfort
prolongation is active
or not
0=inactive; 1 = active
=> cASA-[T022.S031-
2]-SARB-Data-
Mapping-HVAC
TmpFanMod
e
20
8
1
N8 /
PDT_ENUM8
R
IR.in
d
TmpFanMode refers to
the optional process
input property of AB
UHD to indicate on the
Room Unit (e.g. RU-B)
if a temporary HRV fan
mode is active
Enumeration value
- 0: None
- 1: FanBoostMode
- 2: FirePlaceMode
- 3: KitchenHoodMode
TmpFanMod
eRemainTim
e
20
9
1
U16 /
DPT_TimePerio
dSec
R
IR.in
d
TmpFanModeRemain
Time refers to the
optional process input
property of AB UHD
=> cASA-[T022.S035-
2I055] Fan operation:
Fan Boost/Fire
Place/Kitchen Hood