HVAC Products 6 The settings in detail 23. November 2007
Swimming pool
Line no. Operating line
8900 Swimming pool temp
8901 Swimming pool setpoint
Display of the current swimming pool temperature and setpoint.
Primary controller
Line no. Operating line
8930 Primary controller temp
8931 Primary controller setpoint
Display of the current primary controller temperature and setpoint.
Common flow
Line no. Operating line
8950 Common flow temp
8951 Common flow temperature setpoint
8957 Common flow setp refrig
Buffer storage tank
Line no. Operating line
8970 El imm heater buffer
Off
On
8980 Buffer temp 1
8981 Buffer setpoint
8982 Buffer temp 2
8983 Buffer temp 3
8990 Hours run el buffer
8991 Start counter el buffer
Display of the setpoints and actual values of the buffer storage tank and of the number
of operating hours and starts.
Input H1
Line no. Operating line
9000 Flow temp setpoint H1
9001 Flow temp setpoint H2
9004 Flow temp setpoint H3
Display of the temperature setpoint when contact Hx is activated and setting ”Heat
request” is used.
Water pressure
Line no. Operating line
9005 Water pressure H1
9006 Water pressure H2
9009 Water pressure H3
Display of the water pressure when contact Hx is activated and setting ”Pressure
measurement 10 V” is used.