22 / 36
Siemens Room Unit for Boiler Control CE1U2283en
Building Technologies Description of room unit settings 2015-09-16
The programmed heating curve is based on a room setpoint of 20°C. If the room
setpoint is adjusted, the heating curve automatically adapts to the new value.
The summer / winter changeover temperature is the criterion for automatic summer
/ winter changeover of the heating plant.
It offers the following benefits:
· Fully automatic operation throughout the year
· The heating will not be switched on when the outside temperature drops for
short periods of time
· Additional savings function
By changing the setting, the respective periods of time will be shortened or
extended. The change will only affect the heating circuit.
Increase: Winter operation will start earlier
Summer operation will start later .
Decrease: Winter operation will start later
Summer operation will start earlier
To determine changeover, the setting of the summer / winter changeover
temperature
( ± a fixed switching differential) is compared with the attenuated outside
temperature.
Heating OFF (from winter to summer)
Taged > SuWi +1 °C
Heating ON (from summer to winter)
Taged < SuWi -1 °C
This function only acts in automatic mode.
Note
Summer / winter
changeover
temperature (SUWI)
Note