Siemens Room Unit for Boiler Control CE1U2283en
Building Technologies Description of room unit settings 2015-09-16
ON
17
T
SuWi
TAged
°C
H
OFF
t
2284D04en
SuWi
+1 °C
SuWi
-1 °C
16
18
19
20
50 10 15
Legend
TAged Attenuated outside
temperature
SuWi Summer / winter
changeover
temperature
T Temperature
t Time in days
H Heating
The 24-hour heating limit is used to switch the heating on and off in the course of
the day, depending on the outside temperature. This function is used primarily
during spring and autumn to respond to short-term temperature variations.
Example:
Setting line e.g.
Comfort setpoint (TRw) 22 °C
24-hour heating limit (THG) -3 °C
Changeover temperature (TRw-THG) heating off = 19 °C
Switching differential (fixed) -1 °C
Changeover temperature heating on = 18 °C
By changing the value entered, the respective heating periods will be shortened or
extended.
Increase: Heating mode will start earlier,
changeover to ECO later.
Decrease: Heating mode will start later,
changeover to ECO earlier.
· The function is not active in operating mode "Continuously Comfort temperature"
· To give consideration to the building’s thermal dynamics, the outside
temperature will be attenuated
Defines the influence of room temperature setpoint deviations on the controlled
system. The room influence can be activated and deactivated (operating line 75).
Changing this setting has the following impact:
Increase: Authority of room influence will increase
Decrease: Authority of room influence will decrease
24-hour heating limit
(ECO24)
Gain factor of room
influence (KORR)