RUGGEDCOM RX1512
Installation Guide
Chapter 6
Certification
EMC and Environmental Type Tests 37
Test Description Test Levels
Severity
Levels
DC Power Ports
300 V for 1 s
IEC 61000-4-17 Ripple on DC Power Supply DC Power Ports 10% 3
IEC 61000-4-29 Voltage Dips and Interrupts DC Power Ports 30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal ports 2 kV (Failsafe Relay output)Dielectric Strength
DC Power Ports 2 kV
Signal ports 5 kV (Failsafe Relay output)
IEC 60255-5
HV Impulse
DC Power Ports 5 kV
a
Siemens-specified severity levels
EMC Immunity Type Tests for IEEE 1613
NOTE
The RUGGEDCOM RX1512 meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports. Class 1 allows for temporary communication loss, while Class 2 requires
error-free and interrupted communications.
Description Test Levels
Signal ports 5 kV (Failsafe Relay Output)HV Impulse
DC Power Ports 5 kV
Signal ports 2 kVDielectric Strength
DC Power Ports 2 kV
Signal ports ± 4 kV @ 2.5 kHz
DC Power Ports
Fast Transient
Earth ground ports
± 4 kV
Signal ports 2.5 kV common mode @1MHzOscillatory
DC Power Ports 2.5 kV common
1 kV differential mode @ 1 MHz
Radiated RFI Enclosure ports 35 V/m
Enclosure Contact ± 8 kVESD
Enclosure Air ± 15 kV
Environmental Type Tests
Test Description Test Levels
Severity
Levels
IEC 60068-2-1 Cold Temperature Test Ad -40 °C (-40 °F), 16 Hours