Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
2.41 Boost of flow temperature setpoint for
d.h.w. heating (UEBW)
Efficient d.h.w. heating.
To allow the d.h.w. to be heated up, the boiler temperature must be higher than the
d.h.w. setpoint.
Setting range Unit Factory setting
0...30 °C (K) 16
The setting will raise the boiler temperature setpoint when there is demand for d.h.w.
Increase: Heating up time will become shorter
More overshoot
Decrease: Heating up time will become longer
Less overshoot
Using the two settings, the controller generates the boiler temperature setpoint for
d.h.w. heating.
Setting on line 26 Reduced setpoint of d.h.w.
temperature
Setting on line 126 Boost
Total Boiler temperature setpoint
For d.h.w. control, refer to “switching differential of d.h.w.” in index.
Benefit
Description
Setting
Effect
Boiler boost
Note