Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
Check if d.h.w. heating is released
Check wiring and fuse of the charging pump (input test)
Check wiring of the d.h.w. temperature sensor (output test)
2.8.1.8 The room temperature does not agree with the required temperature
level:
Check the room temperature setpoints
Is the required operating mode indicated?
Is automatic operation overridden by the room unit?
Are weekday, time of day and the displayed heating program correct?
Has the heating curve slope been correctly set?
Check wiring of outside sensor
2.8.1.9 Heating plant does not function properly
Check all parameters based on the setting instructions "Heating engineer" and the
operating instructions "End-user". especially the preselection of the double function
Make the input test
Make the output test
Check the electromechanical control thermostat (TR) and the manual reset safety
limit thermostat (STB)
2.8.1.10 Frost protection for the plant does not function at all, or does not
function correctly
Check correct functioning of the burner
Check correct functioning of the pumps
Frost protection for the plant in the case of pump heating circuits with active room
temperature limitation
2.8.1.11 Quick setback or boost heating does not function
Check settings made on the heating engineer's level
Fühler an A6,A7 kontrollieren (Eingangtest).
Check the sensor connected to A6, A7 (input test)
2.8.1.12 Fault status signal; display shows "ER"
For cause of error, refer to section "Parameter settings for end-user" on line 50