EasyManua.ls Logo

Siemens RVL481 - 32 Technical Data

Siemens RVL481
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
112/118
Siemens Heating and D.h.w. Controller RVL481 CE1P2541en
Building Technologies 32 Technical data 20.05.2008
32 Technical data
Rated operating voltage AC 230 V (±10 %)
Frequency 50 Hz
Power consumption (no external load) max. 9 VA
Supply line fusing 10 A
Switching capacity AC 24…230 V
Switching current Y1/K4, Y2/K5, Q1, Y7, Y8 AC 0.02…2 (2) A
Switching current Q5, Q3/Y3, Q4, K6 AC 0.02…1 (1) A
Rated current of ignition transformer max. 1 A (max. 30 s)
Switch-on current of ignition transformer max. 10 A (max. 10 ms)
Copper cable 0.6 mm
20 m
Copper cable 0.5 mm
2
50 m
Copper cable 1.0 mm
2
80 m
Copper cable 1.5 mm
2
120 m
Screw terminals for wire section up to 2.5 mm
2
Bus protocol/type LPB
Bus loading characteristic E 7
Backup of controller clock 12 h
-conformance to
EMC directive
– Immunity
– Emissions
Low voltage directive
– Safety
2004/108/EC
– EN 61000-6-1 / -2
– EN 61000-6-3 / -4
2006/95/EC
– EN 60730-1 / EN 60730-2-9
Safety class II to EN 60730
Degree of protection (cover closed) IP42 to EN 60529
Degree of contamination
2 to EN 60730
Refer to ”Dimensions“
Unit (net) 1.2 kg
Controller insert
Light grey RAL 7035
Terminal base
Pigeon blue RAL 5014
Operation
EN 60721-3-3
Transport
EN 60721-3-2
Storage
EN 60721-3-1
Climatic conditions
class 3K5 class 2K3 class 1K3
Temperature
0…+50 °C –25…+70 °C –20…+65 °C
Humidity
<95 % r.h.
(non-condensing)
<95 % r.h.
<95 % r.h.
(non-condensing)
Mechanical conditions
class 3M2 class 2M2 class 1M2
Use above sea level
max. 3000 m above sea level
Power supply
Output relays
Permissible cable
lengths to sensors
and room unit
Connection terminals
Communication
by wire
Backup
Standards
Protective data
Dimensions
Weight
Colors
Environmental
conditions

Table of Contents