45/118
Siemens Heating and D.h.w. Controller RVL481 CE1P2541en
Building Technologies 10 Function block "Space heating" 20.05.2008
10.6.4 Parallel displacement of heating curve
The heating curve can be displaced parallel:
• Manually with the setting knob for room temperature readjustments. The readjustment
can be made by the enduser and covers a maximum range of
−4.5…+4.5 °C room
temperature
• Manually on operating line 72
The parallel displacement of the heating curve is calculated as follows:
Parallel displacement
∆T
Flow
= ( ∆T
Knob
+ ∆T
Operating line 72
) × ( 1 + s )
10 0 -10 -20
-30
90
80
70
60
50
30
2540D06
100
0
10
10
0
30
T
R
w
T
A
T
V
20
40
Parallel displace-
ment of heating
curve
s Slope
T
A
Outside temperature
T
V
Flow temperature
T
Rw
Room temperature setpoint
10.6.5 Display of setpoints
2 current setpoints result from the basic setting, the position of the setting knob and – if
made – the entry on operating line 72, which can be called up on operating line 166:
• Resultant flow temperature setpoint at an outside temperature of +15 °C
• Resultant flow temperature setpoint at an outside temperature of −5 °C
These 2 current setpoints determine the actual heating curve from which – as a func-
tion of the composite outside temperature – the current flow temperature setpoint is
generated. It can be called up on operating line 165 (also refer to chapter “25 Function
block "Service functions and general settings"").