34/118
Siemens Heating and D.h.w. Controller RVL481 CE1P2541en
Building Technologies 8 Function block "Plant type" 20.05.2008
8 Function block "Plant type"
This function block only contains the selection of the plant type.
8.1 Operating line
Line Function, parameter Factory setting (range) Unit
51 Plant type 1−1 (1−0…6−5)
8.2 General
When commissioning the plant, the respective plant type must be entered first. This
ensures that the functions required for the specific type of plant, the parameters and
operating lines for the settings and displays will be activated.
All plant-specific variables and operating lines existing for the other plant types will then
be hidden. They will not be displayed.
Example for an entry (selection of plant type 1–2)
2540Z02
51
1
2
= operating line
= Heating circuit plant type 1
= d.h.w. circuit type 2