46/118
Siemens Heating and D.h.w. Controller RVL481 CE1P2541en
Building Technologies 10 Function block "Space heating" 20.05.2008
10.7 Generation of setpoint
10.7.1 Weather-compensated control
Weather-compensated control is used with plant types 1−x, 2−x and 3−x. The setpoint is
generated via the heating curve as a function of the outside temperature. The tempera-
ture used is the
composite outside temperature.
2540B01
LPB
SYNERGYR
OZW30
, oder
s
1 + s
20 °C
1 + s
Setting knob
room unit*
Room setpoint
Operating line
1, 2 oder 3
Composite outside
temperature
Heating curve
Setting knob
on controller
Parallel displacement of
heating curve, operating line 72
Setpoint on
operating line 165
Flow temperature
setpoint T
Vw
LPB Data bus
OZW30 SYNERGYR central unit
s Slope
* Active only with room unit level
The impact of the central unit OZW30 is described in section “28.2 Combination with
SYNERGYR central unit OZW30 described.
10.7.2 Demand-compensated control
Demand-compensated control is used with plant types 4−x, 5−x, and 6−x.
The setpoint is delivered to the RVL481 via the data bus (LPB) in the form of a heat de-
mand signal. In that case, the outside temperature will not be taken into consideration.