Siemens Heating and D.h.w. Controller RVL481 CE1P2541en
Building Technologies 3 Fundamentals 20.05.2008
3.4 Heating circuit operating modes
The heating circuit operating mode is selected on the controller by pressing the respec-
tive button. Also, the operating mode can be changed by bridging terminals H1–M.
3.4.1 Automatic operation
Automatic changeover from NORMAL to REDUCED temperature, and vice versa,
according to the 7-day program entered
Automatic changeover to holiday mode, and back, according to the holiday schedule
entered
Demand-dependent switching of the heating system according to the room and outside
temperature while giving consideration to the building's thermal inertia (ECO function)
Remote operation via room unit (optional)
Frost protection is ensured
3.4.2 Continuously REDUCED heating
Continuous heating to the REDUCED temperature
With ECO function
No holiday mode
Remote operation from a room unit not possible
Frost protection is ensured
3.4.3 Continuously NORMAL heating
Continuous heating to NORMAL temperature
No ECO function
No holiday mode
Remote operation via room unit not possible
Frost protection is ensured
3.4.4 Protection mode
Heating is switched off, but is ready to operate
Frost protection is ensured
3.5 D.h.w. operating mode
D.h.w. heating is switched on and off by pressing the respective button:
ON (button
is lit): D.h.w. heating takes place independent of the heating circuit’s
operating mode and control. D.h.w. heating to the NORMAL or REDUCED setpoint
can be provided as follows:
According to the entered switching program 2
According to the entered heating circuit program (–1 h)
Continuously (24 hours a day)
During the entered holiday period, d.h.w. heating and the circulating pump are deac-
tivated when using controllers with no bus connection (with data bus, depending on
the setting made).
OFF (button
dark): No d.h.w. heating. Frost protection is ensured (with the excep-
tion of plant types x–4 and x–5)