EasyManua.ls Logo

Siemens RVL481 - Setpoint Rise; 3-Position Control

Siemens RVL481
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
48/118
Siemens Heating and D.h.w. Controller RVL481 CE1P2541en
Building Technologies 11 Function block "3-position actuator heating circuit" 20.05.2008
11.2.2 Setpoint rise
t
t
2540D07
T
Vw
T
Vw
Maximum rise: =
T
Vw
t
t Time
t Unit of time
TVw Flow temperature setpoint
TVw Rate of setpoint increase per unit of time
The rate of increase of the flow temperature setpoint can be limited to a maximum. In
that case, the maximum rate of increase of the flow temperature setpoint is the selected
temperature per unit of time (°C per hour). This function:
prevents cracking noises in the piping
protects objects and construction materials that are sensitive to quick temperature
increases (e.g. antiquities)
prevents excessive loads on heat generating equipment
This function can be deactivated (setting
---).
During d.h.w. heating, limitation of the rate of increase acts as follows:
Plant type Effect
1–x
3–0
3–2
3–4
3–5
4–x
6–x
Limitation of the rate of increase is always active
3–1
3–3
Limitation of the rate of increase only acts with shifting or
parallel d.h.w. priority
11.3 3-position control
3-position control operates as weather- or demand-compensated PI flow temperature
control. The flow temperature is controlled through a modulating actuating device (slip-
per or seat valve). Owing to the I-part, there is no control offset.
The controller’s positioning commands to the actuator of the actuating device are fed to
the output relays and indicated by LEDs.
Function
Effect on d.h.w. heating

Table of Contents

Other manuals for Siemens RVL481

Related product manuals