4 14.02.00 CM2G3368X1 Siemens Building Technologies / Landis & Staefa Division
en english
Application
The POLYGYR-Ace controlller is used for the control of packaged airconditioning units or heating plant.
Two adigital outputs selectable between 2 stages of on/off control or as a single 3 point controller.
A digital relay contact input is used to select either day/night or summer/winter switch-over as determined by the setting of
the corresponding parameter.
The second analogue input can be used for the following applications:
•
PI Limiter
•
Remote Set point
•
Temperature differential
•
Temperature shift
The setting of the parameters are displayed on the LCD.
The RWC32/RWC82 controller is intended for either DIN rail mounting in a switchboard or screw mounting for external use.
Parameters
(default values in brackets)
Name Description Display, Setting Range Name Description Display, Setting Range
Main Main temperature
−
35...+130 °C
TEMP DIFF Temperature difference mode
Ts Temperature setpoint 0...110 °C (20) TDIFF Temperature difference 0...50 °C (0)
2nd Second analogue input
−
35...+130 °C
TEMP SHIFT Temperature shift mode
D I/P Digital input Enable On Off (Off) SF ST Temperature shift start
−
35...+35 °C (26)
SW / DN SW changeover/ Day night select DN On/ SW 0n (DN 0n) SF ED Temperature shift end
−
35...+35 °C (30)
TS-D Day setpoint 0...110 °C (20) Shift Temperature shift 0... 35 °C (4)
TS-N Night setpoint 0...110 °C (16) O/P1 Output 1 Heat / Cool (Heat)
TS-W Winter setpoint 0...110 °C (20) O/P2 Output 2 Heat / Cool / Off (Cool)
TS-S Summer setpoint 0...110 °C (22) XDZ Dead Zone 0...20 °C (2)
PI limiter PI limiter mode TN Integral time .....(OFF) 16, 32, 64...4096s (128)
MX / MN Max. / Min. limit select Max.On/Min.On (Min.0n) SD1 Switching differential for output 1 0.5...10 °C (1)
TL Limiting temperature 0....110 °C (16) SD2 Switching differential for output 2 0.5...10 °C (1)
REMOTE Remote setpoint mode XP Proportional band for 3 position 1...100 °C (20)
Range 0...50 °C / 0...100 °C 50 / 100 (50) TCYC Actuator cycle time for 3 position 30/90/120/150s (150)
Operating Modes
T
he POLYGYR-Ace has three different operating modes:
•
Setup mode:
Used to configure the controller to the application. In this mode the controller is not in operation.
To get into setup mode:
Press „Select“
for more than 5 seconds. See next pages for explanations of the setup
process.
•
Test mode:
Used to test the functioning of the controller and the installation. The controller operate normally, but
displays the following test values:
Output 1
<
>
Output 2
<
>
Analog Input 1
<
>
Analog Input 2
<
>
Digital Input.
To get into test mode:
Press „Up“
and „Down“
key simultaneously.
•
Normal mode:
As soon as the configuration has been finished, the controller goes into the normal operating mode.
Time-out
From any of the described modes the controller times out back to the normal operating mode.
From setup-mode: after 30 secondes
From test-mode: after 5 minutes