EasyManua.ls Logo

Siemens S7-1500 - Wiring rules

Siemens S7-1500
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product overview, functions
2.6 Requirements for use
CP 1543-1
Operating Instructions, 05/2017, C79000-G8976-C289-07
21
2.6.3
Programming
Program blocks
For communications services, there are preprogrammed program blocks (instructions)
available as the interface in your STEP 7 user program.
Table 2- 1 Instructions for communications services
Protocol
Program block (instruction)
System data type
TCP Establish connection and
send/receive data via:
TSEND_C/TRCV_C or
TCON, TSEND/TRCV
(termination of the connec-
tion using TDISCON possi-
ble)
TCON_IP_v4
TCON_Configured
ISO-on-TCP
TCON_IP_RFC
ISO
TCON_ISOnative
UDP
TCON, TUSEND/TURCV
(termination of the connec-
tion using TDISCON possi-
ble)
TCON_IP_v4
E-mail
TMAIL_C TMail_v4
*
TMail_v6
*
TMAIL_FQDN
*
FTP
FTP_CMD FTP_CONNECT_IPV4
*
FTP_CONNECT_IPV6
*
FTP_CONNECT_NAME
*
FTP_FILENAME*
FTP_FILENAME_PART*
*User-defined data type
Table 2- 2 Instructions for configuration tasks
Function
Program block (instruction)
System data type
Configuration of the Ethernet
interface
T_CONFIG CONF_DATA
Refer to the documentation of the program blocks in the online help of STEP 7.