Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Smart Infrastructure Handling 2019-04-09
> 5s und < 10s (cf. page 24). Full configuration via bus: With a unique
Modbus address, a connection can be established from Modbus
master/programming tool following startup by means of the preset
transmission format and baud rate (or auto-baud)..
With an existing connection, the bus and actuator parameters can be set to target
values via the bus. During write access to the bus parameters,
"1 = Loadā€œ must be written to register 768 within 30 seconds to ensure the changes
are not discarded.