Technical data
11.13 Auxiliary switches and alarm switches
3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
163
Auxiliary switches and alarm switches
Technical data of the auxiliary and alarm switches of the 3VL molded case circuit breakers:
Table 11- 42 Auxiliary switches and alarm switches
Rated insulation voltage U
i
with degree of pollution in accordance with IEC 60947-1
400 V
Class 3
Rated impulse withstand voltage U
imp
Conventional thermal current I
th
Rated operating current I
e
Rated operating voltage U
e
• Alternating current 50 / 60 Hz, AC-12
at U
e
24 V
48 V
110 V
230 V
400 V
I
e
10 A
10 A
10 A
10 A
10 A
• Alternating current 50 / 60 Hz, AC-15
at U
e
24 V
48 V
110 V
230 V
400 V
I
e
6 A
6 A
6 A
6 A
3 A
• Direct current, DC-12
at U
e
24 V
48 V
110 V
I
e
10 A
5 A
2.5 A
• Direct current, DC-13
at U
e
24 V
48 V
110 V
I
e
3 A
1.5 A
0.7 A
Test voltage/test current