Accessories 
  3.4 Rotary operators 
3VA27 molded case circuit breakers & 3WL10 air circuit breakers 
Manual, 10/2018, L1V30499596002-01 
115 
The door interlock of the door mounted rotary operator locks the door as soon as the door 
mounted rotary operator is turned to position ON.  
The door interlock can be overridden by a deliberate action. This is done by pressing the 
door interlocking pin on the left side of the masking plate with a sharp object (e.g. a narrow 
screwdriver). This means that the door can be opened with the operator in position ON so 
that maintenance can be carried out, for example. 
 
The circuit breaker can be locked via the door mounted rotary operator in three different 
ways. 
1.  On the handle: If the circuit breaker on the handle is locked with padlocks (up to three, 5-
7 mm diameter), the door cannot be opened when the circuit breaker is open either. 
2.  On the rotary operator: For locking the circuit breaker while the panel door is open, e.g. 
for maintenance work, padlocks (up to three, 5-7 mm diameter) can also be used on the 
operator itself. 
3.  With cylinder lock on the rotary operator: The circuit breaker can also be prevented from 
closing with a key and an optionally installable cylinder lock.