Application planning 
  4.3 Communication planning 
3VA27 molded case circuit breakers & 3WL10 air circuit breakers 
Manual, 10/2018, L1V30499596002-01 
159 
 
The electrodynamic forces that arise during a short-circuit can result in high mechanical 
loads in and on the switchboard. To minimize the effects, armature plates must be mounted 
in the vicinity of the terminals of the circuit breaker. 
The following diagram shows the distance of the first armature plate depending on the 
prospective short-circuit current when busbars are used: 
 
Distance of the first armature plate to the terminals of the circuit breaker 
Prospective short-circuit current 
If cables are used in the installation, the armature plates must be mounted at a distance of 
150 mm from the connection.