Description   
2.8 Electronic trip unit ETU 
  3VA27 molded case circuit breakers & 3WL10 air circuit breakers 
46  Manual, 10/2018, L1V30499596002-01 
Label for installed internal accessories 
You can make a note of the number of installed accessories on the internal accessories 
label. Accessories that have been pre-installed in the factory are already listed here.  
This tells you which accessories are installed without the need to open the circuit breaker. 
You can use this information, for example, to reorder components. 
The presence of a metering function can also be seen here by the side of the main contacts 
on which the voltage tap is located. (above/below or on the incoming/outgoing side) 
Label of circuit breaker data 
A label is affixed to the left-hand side of the circuit breaker that provides an overview of the 
most important data of the circuit breaker. 
A label is affixed to the left-hand inside of the guide frame that provides an overview again of 
the most important data of the guide frame. 
The article number of the guide frame is stated separately on its label even if it is part of the 
withdrawable breaker version. 
 
As a protection device, the circuit breaker has the task of protecting installations and clearing 
electrical faults occurring in the system. A trip unit detects whether a fault occurs by 
comparing the protection parameters set in it with the measured values. The circuit breaker 
has microprocessor-controlled trip units. 
The tripping characteristic can be adjusted to the required values with numerous possible 
settings. 
Selective tripping and instantaneous release 
On short-circuits in the medium current range, selective tripping (ST) is ensured. On short-
circuits with a larger current and high arc energy in the arc chute, an instantaneous release 
(INST) responds and interrupts the overcurrent immediately (< 30 ms). 
One ETU for two versions of the current-limiting (3VA27) and current-carrying (3WL10) 
contact system 
The kinematic behavior of the two contact systems (ACB/MCCB) of this platform device only 
diverges above the maximum settable operating value of the instantaneous short-circuit 
release (INST). For this reason, it is possible to use the identical ETU (ETU of the 3-series 
and ETU of the 6-series) for both versions.