EasyManua.ls Logo

Siemens SENTRON 3WL10 - Page 146

Siemens SENTRON 3WL10
290 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application planning
4.1 Types of installation and installation locations
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
144 Manual, 10/2018, L1V30499596002-01
Rated opera-
tional current
I
n
[A]
Min. cop-
per cross
section
[mm
2
]
Ambient temperature
< 40 °C
45 °C
50 °C
55 °C
60 °C
65 °C
70 °C
800 500
800
800
800
800
800
750
700
100% 100% 100% 100% 100% 94% 88%
1000 600
1000
1000
1000
971
942
885
827
100%
100%
100%
97%
94%
88%
83%
1250
Bars
2x40x10
800
1250
1250
1250
1184
1118
1049
980
100% 100% 100% 95% 89% 84% 78%
1250
Bars
2x50x10
1000
1250
1250
1250
1240
1182
1122
1057
100% 100% 100% 99% 95% 90% 85%
1600
Bars
2x50x10
1000
1400
1350
1296
1240
1183
1122
1058
88% 84% 81% 78% 74% 70% 66%
1600
Bars
3x50x10
*)
1500
1600
1541
1481
1417
1352
1281
1209
100% 96% 93% 89% 85% 80% 76%
*) Socket head cap screw DIN 7984 M10x50 8.8 required
Withdrawable
for
Rear vertical main circuit connection
Rear connection bars for CuAl cables using cable lug
Rated opera-
tional current
I
n
[A]
Min. cop-
per cross
section
[mm
2
]
Ambient temperature
< 40 °C
45 °C
50 °C
55 °C
60 °C
65 °C
70 °C
800 500
800
800
800
800
800
759
716
100%
100%
100%
100%
100%
95%
89%
1000 600
1000
1000
1000
1000
953
905
853
100%
100%
100%
100%
95%
90%
85%
1250 800 1250 1250 1250 1250 1192 1131 1066
100%
100%
100%
100%
95%
90%
85%
1600 1000
1600
1600
1537
1470
1403
1329
1255
100%
100%
96%
92%
88%
83%
78%

Table of Contents