Application planning
4.1 Types of installation and installation locations
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Manual, 10/2018, L1V30499596002-01
149
2 circuit breakers per panel width section in the switchboard
Circuit breaker power with rear terminals for main circuit connec-
tion
u
630 2 x 40 x 5
800 2 x 50 x 5
1000 2 x 50 x 10 /
2 x 50 x 8
1)
1250 2 x 50 x 10 /
2 x 50 x 8
1)
1)
Horizontally oriented: 2 x 50 x 10 mm / vertically oriented: 2 x 50 x 8 mm
You will find information about the terminals used in Chapter Accessories for connection and
insulation (Page 93).
All other types of connection described (fixed-mounted and withdrawable) can be assumed
analogously with the horizontal rear terminals.