Application planning
4.2 Power supply, grounding, and connection
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Manual, 10/2018, L1V30499596002-01
153
Means of connection, cables
Connections of the fixed-mounted breaker version
Circular conductor termi-
nal,
adapter 4x240
30 21.5 120 to 240
43
[380.6]
The following applies to connecting bars to horizontally / vertically orientable rear terminals
for main circuit connection:
Rated uninterrupted current
I
u
[A]
Horizontally oriented
rear terminals
Vertically oriented
rear terminals
800 2 x 50 x 5 ✓ ✓
1000
2 x 50 x 8 — ✓
1250