EasyManua.ls Logo

Siemens SENTRON 3WL10 - Page 19

Siemens SENTRON 3WL10
290 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description
2.5 Basic properties of the circuit breaker (3WL10 / 3VA27)
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Manual, 10/2018, L1V30499596002-01
17
3WL10 air circuit breaker
The 3WL10 air circuit breaker is a current-carrying circuit breaker with IEC certification
(3WL1) and is an addition to the existing 3WL1 IEC portfolio. It has the following
characteristics:
Frame size 0 (FS 0) with a rated current I
n
of 630 A to 1250 A
Optionally available either as a fixed-mounted version or as a withdrawable version
An especially high I
cw
value (up to 50kA 1s) and an I
cu
value (up to 66kA @440V)
3VA27 molded case circuit breaker
The 3VA27 molded case circuit breaker is a current-limiting circuit breaker with IEC
certification and is an addition to the existing 3VA IEC portfolio. It has the following
characteristics:
Frame size 1600 A with a rated current I
n
of 800 A to 1600 A
Choice of two designs:
as a toggle operating mechanism, e.g. as an additional manual operating mechanism
as a stored energy spring mechanism for integration of internal spring charging motors
(external dimensions are not affected by this)
Optionally available either as a fixed-mounted version or as a withdrawable version
An especially high I
cu
value (up to 110kA @415V) and an I
cw
value (up to 20kA 1s)

Table of Contents

Other manuals for Siemens SENTRON 3WL10

Related product manuals