Description
2.6 Possible uses and portfolio
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
30 Manual, 10/2018, L1V30499596002-01
The trip class T
c
specifies the tripping time T
p
for balanced 3-pole loads, starting from the
cold state, with 7.2 times the set current I
r
according to IEC EN 60947 4-1.
The trip classes with "E" stand for a narrower tolerance band of the tripping time T
p
. These
trip classes can also be implemented with the precise electronic trip units of the 3VA27 /
3WL10 motor starter protectors.
The trip class T
c
itself cannot be set directly on the ETU. This can be calculated by
conversion of the delay time t
r
for the I
2
t characteristic to the tripping time T
p
.
Corresponds to
tripping time T
p
11.5 s 8 s
10 4 s < T
p
< 10 s
p
24.5 s 17 s
p
36 s 25 s
p
The tripping time T
p
for motor protection has its reference point at 7.2 x Ir while the delay
time t
r
for plant protection has the reference point at 6 x I
r
. For this reason, the delay time t
r
and tripping time T
p
are not identical.