EasyManua.ls Logo

Siemens SENTRON 3WL10 - Page 39

Siemens SENTRON 3WL10
290 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description
2.7 Basic unit
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Manual, 10/2018, L1V30499596002-01
37
Mechanical and electrical endurance with regular maintenance in accordance with the
manufacturer's instructions:
Mechanical endurance
I
u
≤ 1000
1250
Operating cycles x
1000
20 20
Fre-
quency
Operating cycles/h 60 60
Electrical endurance 440 V Operating cycles x
1000
8 8
690 V Operating cycles x
1000
8 6.5
Operating cycles/h
30
30
Dimensions and weight:
Dimensions
Fixed-
mounted
breaker
H - with COM
mm
291
H - without terminal cover,
without COM
mm 268
D
mm
183
W
3-pole
mm
214
1)
4-pole
mm
284
1)
Withdrawable
breaker
H
mm
363.5
D
mm
271
W
3-pole
mm
278
4-pole
mm
348
Weight (with
ETU and cur-
rent sensor)
Fixed-mounted breaker
3-pole
kg
14
4-pole kg 16
Withdrawable breaker
3-pole
kg
38
4-pole
kg
43
1)
including both side plates
3VA27 molded case circuit breakers
Poles
3, 4
Rated operational current
A
800, 1000, 1250, 1600
Rated operational voltage
U
e
AC (5060 Hz)
V
690
Rated insulation
voltage
U
i
V 1000
Rated impulse
withstand voltage
U
imp
kV 8