Description
2.8 Electronic trip unit ETU
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Manual, 10/2018, L1V30499596002-01
75
Protection functions of the ETU
Switchover to alternative operating values with
short-time-delayed short-circuit current during
the switch-on phase (inrush adaptation) for
tripping characteristic t=k (fixed) possible
●
Default value: OFF
●
Default value: OFF
Setting range of the switch-on phase (inrush
adaptation)
0.1 to 30 s (in steps of 0.01)
Default value: 0.1
0.1 to 30 s (in steps of 0.01)
Default value: 0.1
Setting range Isd = In x … during the switch-on
phase (inrush adaptation)
0.6 to 10 (in steps of 0.1)
Default value: 10
0.6 to 10
(in steps of 0.1)
INST: Instantaneous short-circuit protection I
i
Protection function can be enabled/disabled
Setting range for operating value I
i
= I
n
x … 1.5 to 15 (in steps of 0.1)
Default value: 2
1)
1.5 to 15 (in steps of 0.1)
Default value: 2
1)
Switchover to alternative operating values with
instantaneous short-circuit current during the
switch-on phase (inrush adaptation) for tripping
characteristic t=k (fixed) possible
●
Default value: OFF
●
Default value: OFF
Setting range of the switch-on phase (inrush
adaptation)
0.10 to 30 s (in steps of 0.01)
Default value: 0.1
1)
0.10 to 30 s (in steps of 0.01)
Default value: 0.1
1)
Setting range I
i
= I
n
x … during the switch-on
phase (inrush adaptation)
1.5 to 15 (in steps of 0.1)
Default value: 1.5
1.5 to 15 (in steps of 0.1)
Default value: 1.5
Neutral protection can be enabled/disabled
N
n
GF: Ground-fault protection
Protection function can be enabled/disabled
Characteristic — I²t / t = constant
Default value: t = constant
Setting range for operating value I
g
= I
n
x … — 0.1 to 1 (in steps of 0.001)
Default value: 0.1
1)
Setting range for delay time t
g
(fixed) t=k — 0.1 to 1 s (in steps of 0.05)
Default value: 0.1s
Tolerance
1)
: The better value
out of ± 10% or ± 40 ms or
50 ms with
Setting range for delay time t
g
at I²t (reference
g
— 0.1 to 1 s (in steps of 0.05)
Ground-fault protection pre-alarm — 50 to 90% x I
r
(in steps of
1%)
Tripping can be deactivated — ●