Description
2.8 Electronic trip unit ETU
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Manual, 10/2018, L1V30499596002-01
83
Metering functions of the ETUs of the 6-series
Reference standard: IEC 61557-12
Metering module
MF required
Phase-to-phase voltage (rms value)
Phase-to-neutral voltage (rms value)
tot
tot
(recorded since installation or last reset)
Metering module
MF required
Active energy kWh E
p
total
E
p
drawn
2% ●
Reactive energy kvarh E
q
total
E
q
drawn
E
q
consumed
2% ●
s
Measuring interval memory of the individual parameters for each interval with a time stamp
Metering module
MF required
Current: smallest and largest
Fixed or syn-
chronizable via
test device
Duration: 5 to
120 min
Number of inter-
vals: 24
Phase-to-phase voltage: smallest
V U
min
, U
max
●
Active power: mean and largest
Reactive power: mean and largest
mean
max
Apparent power: mean and largest
- can be analyzed with the freely available powerservice software
4)
Recording and storage of measured values with high-resolution sampling rate (buffer memory)
Metering module
MF required
g