BusAdapter BA SCRJ/RJ45
9.3 Diagnostics
BusAdapter
Equipment Manual, 08/2020, A5E41449003-AB
53
LED
Meaning Remedy
LK1/LK2
MT
Not relevant
off
No error
-
Not relevant
on
Fiber-optic error
Maintenance demanded: attenua-
tion through the fiber-optic cable
is already so high that operation
will soon no longer be possible.
Causes and measures for the transmission
route:
Replace the fiber-optic cable if damaged
or aged.
Ensure correct installation of the
PROFINET plugs or PROFINET connectors.
Adhere to maximum length of 50 m for
POF cable or 100 m for PCF cable.
Ensure that the FOC connectors fit secure-
ly.